FLC LOW SMOKE & HALOGEN FREE CABLES

Low smoke.
Reliable connections.

Explore single-core, multicore, armoured and control cables.
View construction, specifications and datasheets in one place.

6Product datasheets4Product groupsPDFTechnical specifications

Select “View details” for specifications or “Download PDF” for the datasheet. Use your browser’s Find in Page to search.

Explore products (6)

Single-core cablesFILE 01
Orange non-sheathed single-core FLC-LSHF-SL 600S cable with exposed stranded copper conductor

FLC-LSHF-SL 600SSingle core · Non-sheathed

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Stranded copper conductor
Cross-linked LSHF insulation

1 core · 1.5–630 mm²• PDF 1 page
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Construction
Concentric lay round stranded copper with cross-linked low smoke and halogen free insulation. No separate outer sheath.
Insulation colour
Black is listed; other colours are available on request. The illustration shows the orange option.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table for dimensions and packing.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Read full datasheet — 1 page ↗
Single-core cablesFILE 02
Single-core FLC-LSHF 600S cable showing stranded copper, natural insulation and an orange outer sheath

FLC-LSHF 600SSingle core · LSHF sheathed

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Stranded copper · Natural insulation
Separate LSHF outer sheath

1 core · 1.5–630 mm²• PDF 1 page
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound, natural colour.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Black is listed; other colours are available on request. Orange is shown.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Read full datasheet — 1 page ↗
Multicore power cablesFILE 03
Two-core FLC-LSHF 600M example with blue and brown insulation, copper conductors and an orange outer sheath

FLC-LSHF 600MMulticore · Unarmoured

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Individually insulated copper cores
Filler, wrapping tape and LSHF sheath

2, 3 & 4 cores · 1.5–400 mm²• PDF 3 pages
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound. The two-core illustration shows blue and brown cores; confirm core identification for the selected configuration.
Filler and wrapping
Nonhygroscopic LSHF rod or polypropylene filler, with flame-retardant wrapping tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Black is listed; other colours are available on request. Orange is shown.
Listed configurations
Two, three and four cores, 1.5–400 mm². The product image shows a two-core example. No armour.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Read full datasheet — 3 pages ↗
Armoured cablesFILE 04
Single-core FLC-LSHF 600S with natural insulation, orange bedding, aluminium wire armour and orange outer sheath

FLC-LSHF 600SWith armour · AWA

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Single copper core · LSHF bedding
Aluminium wire armour and LSHF sheath

1 core · 1.5–630 mm²• PDF 1 page
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor and insulation
Concentric lay round stranded copper with natural-coloured cross-linked low smoke and halogen free insulation.
Bedding
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange is listed; other colours are available on request.
Armour
Aluminium wire armour (AWA).
Wrapping tape
Flame-retardant tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Black is listed; orange is shown as an optional colour.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Read full datasheet — 1 page ↗
Armoured cablesFILE 05
Two-core FLC-LSHF 600M example with orange bedding, galvanized steel wire armour and orange outer sheath

FLC-LSHF 600MWith armour · SWA

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Multiple copper cores · LSHF bedding
Steel wire armour and LSHF sheath

2, 3 & 4 cores · 1.5–400 mm²• PDF 3 pages
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound. The Construction text lists natural colour, while the source drawing shows colour-coded cores; confirm identification when ordering.
Filler and bedding
Nonhygroscopic LSHF rod filler and orange LSHF type ST8 bedding.
Armour
Galvanized steel wire armour (SWA), with flame-retardant wrapping tape.
Outer sheath
Orange low smoke and halogen free flame-retardant compound, LSHF type ST8. Other colours are available on request.
Listed configurations
Two, three and four cores, 1.5–400 mm². The product image shows a two-core example.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Read full datasheet — 3 pages ↗
Control cablesFILE 06
Four-core FLC-LSHF 600M control-cable example with black numbered cores, copper conductors and orange outer sheath

FLC-LSHF 600MControl cable · Numbered cores

0.6/1 (1.2) kV · 90 °CIEC 60502-1 · IEC 60332-3 Cat. C

Black insulated, numbered copper cores
Flame-retardant wrapping and LSHF sheath

2–30 cores · 1.5–10 mm²• PDF 6 pages
View details
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation and identification
Cross-linked low smoke and halogen free compound; black cores with number marking.
Filler and wrapping
Nonhygroscopic LSHF rod or polypropylene filler, with flame-retardant wrapping tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Black is listed; other colours are available on request. Orange is shown.
Listed configurations
2–30 cores; listed conductor sizes are 1.5, 2.5, 4, 6 and 10 mm². The product image shows a four-core example.
Flame propagation categories
The reference section lists IEC 60332-3 categories A, B and C. The footnote identifies the tabulated product codes as Category C.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; IEC 60332-3; IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.