Explore FRC products (6)

Single-core cables FILE 01
Illustrative FRC-SL 600S single-core cable with stranded copper, mica fire barrier and orange insulation; no separate sheath

FRC-SL 600S Single core · Non-sheathed

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Stranded copper · Mica fire barrier
Cross-linked LSHF insulation

1 core · 1.5–630 mm² • PDF 1 page
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around the conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Construction
Concentric lay round stranded copper, mineral ceramic (mica) fire-resistant tape and cross-linked low smoke and halogen free insulation. No separate outer sheath.
Insulation colour
Orange. Other colours are available on request.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table for dimensions and packing.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 1 page ↗
Single-core cables FILE 02
Illustrative FRC-XL 600S single-core cable with copper, mica tape, natural-coloured insulation and orange sheath

FRC-XL 600S Single core · LSHF sheathed

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Stranded copper · Mica fire barrier
Natural insulation and LSHF sheath

1 core · 1.5–630 mm² • PDF 1 page
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around the conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound, natural colour.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange. Other colours are available on request.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 1 page ↗
Multicore power cables FILE 03
Illustrative FRC-XL 600M two-core power cable with blue and brown insulation, mica barriers and orange sheath

FRC-XL 600M Multicore · Unarmoured

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Copper cores with mica fire barrier
Filler, wrapping tape and LSHF sheath

2, 3 & 4 cores · 1.5–400 mm² • PDF 3 pages
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around each conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound. Core colours: 2 cores — blue and brown; 3 cores — brown, black and grey; 4 cores — blue, brown, black and grey.
Filler and wrapping
Nonhygroscopic LSHF rod or polypropylene filler, with flame-retardant wrapping tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange. Other colours are available on request.
Listed configurations
Two, three and four cores, 1.5–400 mm². The product image shows a two-core example. No armour.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 3 pages ↗
Armoured cables FILE 04
Illustrative FRC-XL 600S armoured single-core cable with mica barrier, aluminium wire armour and orange sheath

FRC-XL 600S With armour · AWA

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Single copper core · Mica fire barrier
Aluminium wire armour and LSHF sheath

1 core · 1.5–630 mm² • PDF 1 page
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around the conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor and insulation
Concentric lay round stranded copper with natural-coloured cross-linked low smoke and halogen free insulation.
Bedding
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange is listed; other colours are available on request.
Armour
Aluminium wire armour (AWA).
Wrapping tape
Flame-retardant tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange. Other colours are available on request.
Listed sizes
Single core; size designations from 1C × 1.5 to 1C × 630 mm². Refer to the PDF table.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 1 page ↗
Armoured cables FILE 05
Illustrative FRC-XL 600M armoured two-core cable with mica barriers, steel wire armour and orange sheath

FRC-XL 600M With armour · SWA

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Copper cores with mica fire barrier
Steel wire armour and LSHF sheath

2, 3 & 4 cores · 1.5–400 mm² • PDF 3 pages
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around each conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation
Cross-linked low smoke and halogen free compound. The Construction text lists natural colour, while the source drawing shows colour-coded cores; confirm identification when ordering.
Filler and bedding
Nonhygroscopic LSHF rod filler and orange LSHF type ST8 bedding.
Armour
Galvanized steel wire armour (SWA), with flame-retardant wrapping tape.
Outer sheath
Orange low smoke and halogen free flame-retardant compound, LSHF type ST8. Other colours are available on request.
Listed configurations
Two, three and four cores, 1.5–400 mm². The product image shows a two-core example.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 3 pages ↗
Control cables FILE 06
Illustrative FRC-XL 600M control cable with four numbered black cores, mica barriers and orange sheath

FRC-XL 600M Control cable · Numbered cores

0.6/1 (1.2) kV · 90 °C BS 6387 CWZ · IEC 60502-1
IEC 60332-3 Cat. C

Numbered black cores · Mica fire barrier
Flame-retardant wrap and LSHF sheath

2–30 cores · 1.5–10 mm² • PDF 6 pages
View details
Fire barrier
Mineral ceramic (mica) fire-resistant tape around each conductor.
Applications
Installation in conduits and open trays, as described in the datasheet.
Conductor
Concentric lay round stranded copper.
Insulation and identification
Cross-linked low smoke and halogen free compound; black cores with number marking.
Filler and wrapping
Nonhygroscopic LSHF rod or polypropylene filler, with flame-retardant wrapping tape.
Outer sheath
Low smoke and halogen free flame-retardant compound, LSHF type ST8. Orange. Other colours are available on request.
Listed configurations
2–30 cores; listed conductor sizes are 1.5, 2.5, 4, 6 and 10 mm². The product image shows a four-core example.
Flame propagation categories
The reference section lists IEC 60332-3 categories A, B and C. The footnote identifies the tabulated product codes as Category C.
Voltage and temperature
Rated voltage 0.6/1 (1.2) kV; circuit voltage not exceeding 1,000 V. Maximum conductor temperature 90 °C.
AC test voltage
3.5 kV.
Reference standards
IEC 60502-1; BS 6387 (Category CWZ); IEC 60332-3 (Category C); IEC 61034; IEC 60754-1; IEC 60754-2.
Standard packing
Refer to the PDF table for the selected size and core configuration.
Product illustration
Illustrative construction, not to scale. Refer to this model’s PDF for the specified configuration and dimensions.
Read full datasheet — 6 pages ↗